Connection of Surge Protection Device (SPD)

Connection of Surge Protection Device (SPD)

Connections of a SPD to the loads should be as short as possible in order to reduce the value of the voltage protection level (installed Up) on the terminals of the protected equipment.

The total length of SPD connections to the network and the earth terminal block should not exceed 50 cm.

One of the essential characteristics for the protection of equipment is the maximum voltage protection level (installed Up) that the equipment can withstand at its terminals. Accordingly, a SPD should be chosen with a voltage protection level Up adapted to protection of the equipment (see Fig. 1). The total length of the connection conductors is

L = L1+L2+L3.

For high-frequency currents, the impedance per unit length of this connection is approximately 1 µH/m

Hence, applying Lenz’s law to this connection: ΔU = L di/d

The normalized 8/20 µs current wave, with a current amplitude of 8 kA, accordingly creates a voltage rise of 1000 V per metre of cable.

ΔU =1 x 10-6 x 8 x 103 /8 x 10-6 = 1000 V


Fig. 1 – Connections of a SPD L < 50 cm

As a result the voltage across the equipment terminals, U equipment, is:

U equipment = Up + U1 + U2

If L1+L2+L3 = 50 cm, and the wave is 8/20 µs with an amplitude of 8 kÂ, the voltage across the equipment terminals will be Up + 500 V.

Connection in plastic enclosure

Figure 2 below shows how to connect a SPD in plastic enclosure.

Fig. 2 – Example of connection in plastic enclosure

Connection in metallic enclosure

In the case of a switchgear assembly in a metallic enclosure, it may be wise to connect the SPD directly to the metallic enclosure, with the enclosure being used as a protective conductor (see Fig. 3).

This arrangement complies with standard IEC 61439-2 and the Assembly manufacturer must make sure that the characteristics of the enclosure make this use possible.

Fig. 3 – Example of connection in metallic enclosure

Conductor cross section

The recommended minimum conductor cross section takes into account:

1. The normal service to be provided: Flow of the lightning current wave under a maximum voltage drop (50 cm rule).

    Note: Unlike applications at 50 Hz, the phenomenon of lightning being high-frequency, the increase in the conductor cross section does not greatly reduce its high-frequency impedance.

2. The conductors’ withstand to short-circuit currents: The conductor must resist a short-circuit current during the maximum protection system cutoff time.

    IEC 60364 recommends at the installation incoming end a minimum cross section of:

    a. 4 mm2 (Cu) for connection of Type 2 SPD;

    b. 16 mm2 (Cu) for connection of Type 1 SPD (presence of lightning protection system).

Related Posts

Introduction to SPD and its role

Introduction to SPD and its role

In an electrical systems, SPDs are usually installed in tap-off configuration (in parallel) between the live conductors and the earth. The operating principle of SPD can be similar to that of a circuit breaker. In normal use (no overvoltage): the SPD is similar to an open circuit breaker. When there is an overvoltage: the SPD […]

Differences Between Surge Arrester And Surge Protection Device

Differences Between Surge Arrester And Surge Protection Device

Surge protection devices (SPD) and surge arresters have the same function: they can protect electrical equipment from overvoltage conditions, but what is the difference between them? The following is a brief description of the differences between them. 1. Different Rated Voltages: According to NEC 2017 Sec 280 & 285, the rated voltage of the surge […]

How to choose the right surge protector?

How to choose the right surge protector?

How to choose the right surge protector? Choosing the right surge protective device (SPD) and protective circuit breakers involves considering a wide range of parameters related to types of SPDs, circuit breaker arrangements, and risk assessment. Three rules of thumb for choosing surge protection Now that we’ve established that SPDs should be at the heart […]