Propagation of a lightning wave

Propagation of a lightning wave

Electrical networks are low-frequency and, as a result, propagation of the voltage wave is instantaneous relative to the frequency of the phenomenon: at any point of a conductor, the instantaneous voltage is the same.

The lightning wave is a high-frequency phenomenon (several hundred kHz to a MHz):

1.       The lightning wave is propagated along a conductor at a certain speed relative to the frequency of the phenomenon. As a result, at any given time, the voltage does not have the same value at all points on the medium (see Fig. 1).


Fig. 1 – Propagation of a lightning wave in a conductor

1.    A change of medium creates a phenomenon of propagation and/or reflection of the wave depending on:

2.1 the difference of impedance between the two media;

2.2 the frequency of the progressive wave (steepness of the rise time in the case of a pulse);

2.3 the length of the medium.

In the case of total reflection in particular, the voltage value may double.

Example: case of protection by a SPD

Modelling of the phenomenon applied to a lightning wave and tests in laboratory showed that a load powered by 30 m of cable protected upstream by a SPD at voltage Up sustains, due to reflection phenomena, a maximum voltage of 2 x Up (see Fig. 2). This voltage wave is not energetic.

Fig. 2 – Reflection of a lightning wave at the termination of a cable

Corrective action

Of the three factors (difference of impedance, frequency, distance), the only one that can really be controlled is the length of cable between the SPD and the load to be protected. The greater this length, the greater the reflection.

Generally for the overvoltage fronts faced in a building, reflection phenomena are significant from 10 m and can double the voltage from 30 m (see Fig. 3).

It is necessary to install a second SPD in fine protection if the cable length exceeds 10 m between the incoming-end SPD and the equipment to be protected.

Related Posts

The Widely Usage of Solar Connectors in the Renewable Energy Industry

The Widely Usage of Solar Connectors in the Renewable Energy Industry

As the world is moving towards renewable energy, solar power has gained a lot of interest from people and businesses alike. With the growing demand for solar power, the need for solar connectors has increased significantly. The widely usage of solar connectors in the renewable energy industry is undeniable. 1. Solar connectors are essential components in solar […]

Elements of the protection system

Elements of the protection system

A SPD must always be installed at the origin of the electrical installation. Location and type of SPD The type of SPD to be installed at the origin of the installation depends on whether or not a lightning protection system is present. If the building is fitted with a lightning protection system (as per IEC […]

Connection of Surge Protection Device (SPD)

Connection of Surge Protection Device (SPD)

Connections of a SPD to the loads should be as short as possible in order to reduce the value of the voltage protection level (installed Up) on the terminals of the protected equipment. The total length of SPD connections to the network and the earth terminal block should not exceed 50 cm. One of the […]