GENERAL INFORMATION
l Two-pole/ Three pole/ Four pole varistor surge protective device (AC SPD)
l Combined SPD Type 1&2 with MOV and CDGG technology for use in different power system.
l Visual indication and optional remote contact signaling(S), capable of protecting Terminal equipment.
l Non-follow current.
l The Prewired complete unit consisting of a base part and replaceable plug-in protection modules.
l Installation at the boundaries from zone LPZ 0A to LPZ 2.
l Installation at the boundary of zones LPZ1 and LPZ2
l Use for the direct lightning protection in Power system, can usage in Transformer low-voltage side.
l DIN rail installation.
SPECIFICATIONS
l SPD according to EN 61643-11/IEC 61643-11: Type 1+2/ Class Ⅰ+Ⅱ
l Max. continuous operating voltage (a.c.) (Uc): 385V (50/60Hz)
l Temporary overvoltage (TOV): 385V/5s-withstand
l Lightning impulse current (10/350µs) (Iimp): 12.5kA
l Nominal discharge current (8/20µs) (In): 20kA
l Max. discharge current (8/20µs) (Imax): 50kA
l Voltage protection level (Up): ≤2.2kV