Overvoltage may occur in electrical installations for various reasons. It may be caused by:

1. The distribution network as a result of lightning or any work carried out.

2. Lightning strikes (nearby or on buildings and PV installations, or on lightning conductors).

3. Variations in the electrical field due to lightning.

Like all outdoor structures, PV installations are exposed to the risk of lightning which varies from region to region. Preventive and arrest systems and devices should be in place.


Protection by equipotential bonding

The first safeguard to put in place is a medium (conductor) that ensures equipotential bonding between all the conductive parts of a PV installation.

The aim is to bond all grounded conductors and metal parts and so create equal potential at all points in the installed system.


Protection by surge protection devices (SPDs)

    SPDs are particularly important to protect sensitive electrical equipments like AC/DC Inverter, monitoring devices and PV modules, but also other sensitive equipments powered by the 230 VAC electrical distribution n twork. The following method of risk assessment is based on the evaluation of the critical length Lcrit and its comparison with L the cumulative length of the d.c. lines.

SPD protection is required if L ≥ Lcrit .

Lcrit depends on the type of PV installation and is calculated as the following table (Fig. 1) sets out:


Fig. 1 – SPD DC choice

Type of installation

Individual residential premises

Terrestrial production plant

Service/Industrial/Agricultural/Buildings

Lcrit (in m)

115/Ng

200/Ng

450/Ng

L Lcrit

Surge protective device(s) compulsory on DC side

L < Lcrit

Surge protective device(s) not compulsory on DC side


L is the sum of:

1. the sum of distances between the inverter(s) and the junction box(es), taking into account that the lengths of cable located in the same conduit are counted only once, and

2. the sum of distances between the junction box and the connection points of the photovoltaic modules forming the string, taking into account that the lengths of cable located in the same conduit are counted only once.

Ng is arc lightning density (number of strikes/km2/year).


Fig. 2 – SPD selection

SPD Protection

Location

PV modules or Array boxes

Inverter DC side

Inverter AC side

Main board

LDC

LAC

Lightning rod

Criteria

< 10 m

> 10 m

< 10 m

> 10 m

Yes

No

Type of SPD

No need

"SPD 1"

Type 2

"SPD 2"

Type 2

No need

"SPD 3"

Type 2

"SPD 4"

Type 1

"SPD 4"

Type 2 if Ng > 2.5 & overhead line


Installing an SPD

The number and location of SPDs on the DC side depend on the length of the cables between the solar panels and inverter. The SPD should be installed in the vicinity of the inverter if the length is less than 10 metres. If it is greater than 10 metres, a second SPD is necessary and should be located in the box close to the solar panel, the first one is located in the inverter area.

To be efficient, SPD connection cables to the L+ / L- network and between the SPD’s earth terminal block and ground busbar must be as short as possible – less than 2.5 metres (d1+d2<50 cm).

Safe and reliable photovoltaic energy generation

Depending on the distance between the "generator" part and the "conversion" part, it may be necessary to install two surge arresters or more, to ensure protection of each of the two parts.




Fig. 3 – SPD location