Common characteristics of SPDs according to the installation characteristics

Common characteristics of SPDs according to the installation characteristics

Operating voltage Uc

Depending on the system earthing arrangement, the maximum continuous operating voltage Uc of SPD must be equal to or greater than the values shown in the table in Figure 1.

Fig.1 – Stipulated minimum value of Uc for SPDs depending on the system earthing arrangement (based on Table 534.2 of the IEC 60364-5-53 standard)

SPDs connected between (as applicable)System configuration of distribution network
TN systemTT systemIT system
Line conductor and neutral conductor1.1 U / √31.1 U / √31.1 U / √3
Line conductor and PE conductor1.1 U / √31.1 U / √31.1 U
Line conductor and PEN conductor1.1 U / √3N/AN/A
Neutral conductor and PE conductorU / √3U / √31.1 U / √3

Attn: N/A: not applicable

    U: line-to-line voltage of the low-voltage system

The most common values of Uc chosen according to the system earthing arrangement.

TT, TN: 260, 320, 340, 350 V

IT: 440, 460 V

Voltage protection level Up (at In)

The IEC 60364-4-44 standard helps with the choice of the protection level Up for the SPD in function of the loads to be protected. The table of Figure 2 indicates the impulse withstand capability of each kind of equipment.

Fig. 2 – Required rated impulse voltage of equipment Uw (table 443.2 of IEC 60364-4-44)

Nominal voltage of the installation (V)Voltage line to neutral derived from nominal voltages a.c. or d.c. up to and including (V)Required rated impulse withstand voltage of equipment (kV)
Overvoltage category IV (equipment with very high rated impulse voltage)Overvoltage category III (equipment with high rated impulse voltage)Overvoltage category II (equipment with normal rated impulse voltage)Overvoltage category I (equipment with reduced rated impulse voltage)
For example, energy meter, telecontrol systemsFor example, distribution boards, switches socket-outletsFor example, distribution domestic appliances, toolsFor example, sensitive electronic equipment
120/20815042.51.50.8
230/400300642.51.5
277/480
400/6906008642.5
1000100012864
1500 d.c.1500 d.c.86

SPD has a voltage protection level Up that is intrinsic, i.e. defined and tested independently of its installation. In practice, for the choice of Up performance of a SPD, a safety margin must be taken to allow for the overvoltages inherent in the installation of the SPD (see Figure 3).

Fig. 3– Installed Up

The “installed” voltage protection level Up generally adopted to protect sensitive equipment in 230/400 V electrical installations is 2.5 kV (overvoltage category II, see Fig. 4).

Number of poles

Depending on the system earthing arrangement, it is necessary to provide for a SPD architecture ensuring protection in common mode (CM) and differential mode (DM).

Fig. 4 – Protection need according to the system earthing arrangement

TTTN-CTN-SIT
Phase-to-neutral (DM)RecommendedRecommendedNot useful
Phase-to-earth (PE or PEN) (CM)YesYesYesYes
Neutral-to-earth (PE) (CM)YesYesYes

Note:

1.       Common-mode overvoltage

A basic form of protection is to install a SPD in common mode between phases and the PE (or PEN) conductor, whatever the type of system earthing arrangement used.

2.       Differential-mode overvoltage

In the TT and TN-S systems, earthing of the neutral results in an asymmetry due to earth impedances which leads to the appearance of differential-mode voltages, even though the overvoltage induced by a lightning stroke is common-mode.

2P, 3P and 4P SPDs

(see Fig. 5)

1.       These are adapted to the IT, TN-C, TN-C-S systems.

2.       They provide protection merely against common-mode overvoltages.

Fig. 5– 1P, 2P, 3P, 4P SPDs

1P + N, 3P + N SPDs

(see Fig. 6)

1.       These are adapted to the TT and TN-S systems.

2.       They provide protection against common-mode and differential-mode overvoltages

Related Posts

Something About T2 DC Surge Protection Device (DC SPD)

Something About T2 DC Surge Protection Device (DC SPD)

DC Surge Protection Device ( DC SPD) is designed to limit transient over voltages of atmospheric origin and divert current waves to earth, so as to limit the amplitude of this over voltage to a value that is not hazardous for the electrical installation and electric switchgear. Type 2 DC Surge Protection Device ( DC SPD): […]

Propagation of a lightning wave

Propagation of a lightning wave

Electrical networks are low-frequency and, as a result, propagation of the voltage wave is instantaneous relative to the frequency of the phenomenon: at any point of a conductor, the instantaneous voltage is the same. The lightning wave is a high-frequency phenomenon (several hundred kHz to a MHz): 1.       The lightning wave is propagated along a […]

What is DC SPD?

What is DC SPD?

DC SPD applied to the Din rail type protects the DC electric system from surge. Also, the system allows replacement of the protective element (MOV), ensuring convenience and reduced cost. However, as only the protective module is provided, other components should be added when the system is installed in accordance with the site condition.