Common characteristics of SPDs according to the installation characteristics

Common characteristics of SPDs according to the installation characteristics

Operating voltage Uc

Depending on the system earthing arrangement, the maximum continuous operating voltage Uc of SPD must be equal to or greater than the values shown in the table in Figure 1.

Fig.1 – Stipulated minimum value of Uc for SPDs depending on the system earthing arrangement (based on Table 534.2 of the IEC 60364-5-53 standard)

SPDs connected between (as applicable)System configuration of distribution network
TN systemTT systemIT system
Line conductor and neutral conductor1.1 U / √31.1 U / √31.1 U / √3
Line conductor and PE conductor1.1 U / √31.1 U / √31.1 U
Line conductor and PEN conductor1.1 U / √3N/AN/A
Neutral conductor and PE conductorU / √3U / √31.1 U / √3

Attn: N/A: not applicable

    U: line-to-line voltage of the low-voltage system

The most common values of Uc chosen according to the system earthing arrangement.

TT, TN: 260, 320, 340, 350 V

IT: 440, 460 V

Voltage protection level Up (at In)

The IEC 60364-4-44 standard helps with the choice of the protection level Up for the SPD in function of the loads to be protected. The table of Figure 2 indicates the impulse withstand capability of each kind of equipment.

Fig. 2 – Required rated impulse voltage of equipment Uw (table 443.2 of IEC 60364-4-44)

Nominal voltage of the installation (V)Voltage line to neutral derived from nominal voltages a.c. or d.c. up to and including (V)Required rated impulse withstand voltage of equipment (kV)
Overvoltage category IV (equipment with very high rated impulse voltage)Overvoltage category III (equipment with high rated impulse voltage)Overvoltage category II (equipment with normal rated impulse voltage)Overvoltage category I (equipment with reduced rated impulse voltage)
For example, energy meter, telecontrol systemsFor example, distribution boards, switches socket-outletsFor example, distribution domestic appliances, toolsFor example, sensitive electronic equipment
120/20815042.51.50.8
230/400300642.51.5
277/480
400/6906008642.5
1000100012864
1500 d.c.1500 d.c.86

SPD has a voltage protection level Up that is intrinsic, i.e. defined and tested independently of its installation. In practice, for the choice of Up performance of a SPD, a safety margin must be taken to allow for the overvoltages inherent in the installation of the SPD (see Figure 3).

Fig. 3– Installed Up

The “installed” voltage protection level Up generally adopted to protect sensitive equipment in 230/400 V electrical installations is 2.5 kV (overvoltage category II, see Fig. 4).

Number of poles

Depending on the system earthing arrangement, it is necessary to provide for a SPD architecture ensuring protection in common mode (CM) and differential mode (DM).

Fig. 4 – Protection need according to the system earthing arrangement

TTTN-CTN-SIT
Phase-to-neutral (DM)RecommendedRecommendedNot useful
Phase-to-earth (PE or PEN) (CM)YesYesYesYes
Neutral-to-earth (PE) (CM)YesYesYes

Note:

1.       Common-mode overvoltage

A basic form of protection is to install a SPD in common mode between phases and the PE (or PEN) conductor, whatever the type of system earthing arrangement used.

2.       Differential-mode overvoltage

In the TT and TN-S systems, earthing of the neutral results in an asymmetry due to earth impedances which leads to the appearance of differential-mode voltages, even though the overvoltage induced by a lightning stroke is common-mode.

2P, 3P and 4P SPDs

(see Fig. 5)

1.       These are adapted to the IT, TN-C, TN-C-S systems.

2.       They provide protection merely against common-mode overvoltages.

Fig. 5– 1P, 2P, 3P, 4P SPDs

1P + N, 3P + N SPDs

(see Fig. 6)

1.       These are adapted to the TT and TN-S systems.

2.       They provide protection against common-mode and differential-mode overvoltages

Related Posts

Propagation of a lightning wave

Propagation of a lightning wave

Electrical networks are low-frequency and, as a result, propagation of the voltage wave is instantaneous relative to the frequency of the phenomenon: at any point of a conductor, the instantaneous voltage is the same. The lightning wave is a high-frequency phenomenon (several hundred kHz to a MHz): 1.       The lightning wave is propagated along a […]

Type 2-Surge protective Device PV DC SPD

Type 2-Surge protective Device PV DC SPD

GENERAL INFORMATION l Two-module/ Three-module varistor photovoltaic surge protective device (PV DC SPD) l Visual indication and optional remote contact signaling(S) for use in the DC side of PV systems. l The Prewired complete unit consisting of a base part and replaceable plug-in protection modules. l In case of insulation faults in the generator circuit, […]

Introducing of MC4 connectors

Introducing of MC4 connectors

Background While small solar panels used for battery charging and similar tasks may not require special connectors, larger systems normally connect the panels together in series to form strings. In the past this was accomplished by opening a small electrical box on the back of the panel and connecting user-supplied wires to screw terminals within. […]