Common characteristics of SPDs according to the installation characteristics

Common characteristics of SPDs according to the installation characteristics

Operating voltage Uc

Depending on the system earthing arrangement, the maximum continuous operating voltage Uc of SPD must be equal to or greater than the values shown in the table in Figure 1.

Fig.1 – Stipulated minimum value of Uc for SPDs depending on the system earthing arrangement (based on Table 534.2 of the IEC 60364-5-53 standard)

SPDs connected between (as applicable)System configuration of distribution network
TN systemTT systemIT system
Line conductor and neutral conductor1.1 U / √31.1 U / √31.1 U / √3
Line conductor and PE conductor1.1 U / √31.1 U / √31.1 U
Line conductor and PEN conductor1.1 U / √3N/AN/A
Neutral conductor and PE conductorU / √3U / √31.1 U / √3

Attn: N/A: not applicable

    U: line-to-line voltage of the low-voltage system

The most common values of Uc chosen according to the system earthing arrangement.

TT, TN: 260, 320, 340, 350 V

IT: 440, 460 V

Voltage protection level Up (at In)

The IEC 60364-4-44 standard helps with the choice of the protection level Up for the SPD in function of the loads to be protected. The table of Figure 2 indicates the impulse withstand capability of each kind of equipment.

Fig. 2 – Required rated impulse voltage of equipment Uw (table 443.2 of IEC 60364-4-44)

Nominal voltage of the installation (V)Voltage line to neutral derived from nominal voltages a.c. or d.c. up to and including (V)Required rated impulse withstand voltage of equipment (kV)
Overvoltage category IV (equipment with very high rated impulse voltage)Overvoltage category III (equipment with high rated impulse voltage)Overvoltage category II (equipment with normal rated impulse voltage)Overvoltage category I (equipment with reduced rated impulse voltage)
For example, energy meter, telecontrol systemsFor example, distribution boards, switches socket-outletsFor example, distribution domestic appliances, toolsFor example, sensitive electronic equipment
120/20815042.51.50.8
230/400300642.51.5
277/480
400/6906008642.5
1000100012864
1500 d.c.1500 d.c.86

SPD has a voltage protection level Up that is intrinsic, i.e. defined and tested independently of its installation. In practice, for the choice of Up performance of a SPD, a safety margin must be taken to allow for the overvoltages inherent in the installation of the SPD (see Figure 3).

Fig. 3– Installed Up

The “installed” voltage protection level Up generally adopted to protect sensitive equipment in 230/400 V electrical installations is 2.5 kV (overvoltage category II, see Fig. 4).

Number of poles

Depending on the system earthing arrangement, it is necessary to provide for a SPD architecture ensuring protection in common mode (CM) and differential mode (DM).

Fig. 4 – Protection need according to the system earthing arrangement

TTTN-CTN-SIT
Phase-to-neutral (DM)RecommendedRecommendedNot useful
Phase-to-earth (PE or PEN) (CM)YesYesYesYes
Neutral-to-earth (PE) (CM)YesYesYes

Note:

1.       Common-mode overvoltage

A basic form of protection is to install a SPD in common mode between phases and the PE (or PEN) conductor, whatever the type of system earthing arrangement used.

2.       Differential-mode overvoltage

In the TT and TN-S systems, earthing of the neutral results in an asymmetry due to earth impedances which leads to the appearance of differential-mode voltages, even though the overvoltage induced by a lightning stroke is common-mode.

2P, 3P and 4P SPDs

(see Fig. 5)

1.       These are adapted to the IT, TN-C, TN-C-S systems.

2.       They provide protection merely against common-mode overvoltages.

Fig. 5– 1P, 2P, 3P, 4P SPDs

1P + N, 3P + N SPDs

(see Fig. 6)

1.       These are adapted to the TT and TN-S systems.

2.       They provide protection against common-mode and differential-mode overvoltages

Related Posts

Some Tips to Prevent Damage to Surge Protective Devices

Some Tips to Prevent Damage to Surge Protective Devices

Following in the footsteps of the previous article, let’s look at some tips to prevent the damage to surge protective devices (SPDs). 1. Overvoltage Conditions As surge protective devices (SPDs) break is due to overvoltage conditions, choosing a suitable voltage for the surge protective devices (SPDs) is important. 2. Burn-in of Surge Protective Devices (SPDs) […]

Understanding Surge Protective Devices: What They Are and Why You Need Them

Understanding Surge Protective Devices: What They Are and Why You Need Them

Surge protective devices are crucial components of any electrical installation. They play a vital role in protecting your devices and equipment from voltage spikes and surges. But what are they exactly? In this blog post, we’ll take a closer look at surge protective devices and why they are essential for your home or business.   […]

What is the difference between a surge protector and a surge arrester?

What is the difference between a surge protector and a surge arrester?

In lightning protection products, surge protectors and arresters are widely used. Both are important components to protect electronic equipment. There are also fundamental differences. Let us first see what these two lightning protection products are. The surge protector is to limit the instantaneous overvoltage that enters the power line and signal transmission line within the voltage range […]